R-32 vs R-454B: Which Refrigerant Is Better for Your Equipment?

The brand you install decides the refrigerant. Daikin, Goodman and Amana build their new U.S. split systems for R-32. Carrier, Trane, Lennox, York, Mitsubishi Electric and Rheem chose R-454B for their main ducted lines.

235points of R-454B headroom under the 700 GWP limit, vs 25 for R-32

Every number on this page links to the refrigerant maker, the equipment maker or the U.S. Environmental Protection Agency (EPA). Our methodology page explains how we check sources.

Quick answer

Daikin and Goodman use R-32; Carrier, Trane, Lennox, Rheem, Mitsubishi Electric, York and others use R-454B. Both are A2L refrigerants, and neither goes into an R-410A machine. The brand you service decides which refrigerant you handle.

Within a brand, compare the matched model's certified efficiency, charge instructions, safety requirements, warranty and local supply. Transition rules: our R-454B and A2L refrigerant guide.

Key facts:

  • Both are A2L refrigerants and both sit under the 700 GWP limit for new residential and light-commercial AC and heat pumps.
  • R-32 is pure difluoromethane; R-454B is a 68.9 / 31.1 blend of R-32 and R-1234yf.
  • Each needs equipment built and listed for it; neither goes into an existing R-410A unit.

Which brands use R-32 and which use R-454B?

Check the equipment brand first, because each manufacturer chose one refrigerant for its main U.S. line after January 1, 2025.

BrandRefrigerant in new U.S. equipmentOfficial source
DaikinR-32 in the commercial VRV EMERION lineDaikin commercial product announcement. Verified November 20, 2026.
GoodmanR-32 in split air conditioners and heat pumpsGoodman GLXS4B product page
AmanaR-32 in split air conditioners and heat pumps (AXV9S, ALXS5B and others)Amana R-32 split-system brochure, April 2025
CarrierR-454B (Puron Advance) in residential ducted, ductless and light commercialCarrier announcement
TraneR-454B in residential AC and heat pumps and in Precedent rooftop unitsTrane XR14 product page; Precedent rooftop page
LennoxR-454B for whole-home systems; R-32 for ductless mini-splitsLennox R-454B page
YorkR-454B (Opteon XL41) in residential, light commercial and commercial ducted equipmentJohnson Controls refrigerant transition page
Mitsubishi Electric (U.S.)R-454B in its new FX, GX and Smart Multi linesMitsubishi Electric Trane HVAC US release, April 17, 2025
RheemR-454B as its primary refrigerantRheem 2025 refrigerant article
BoschR-454B in its IDS Plus ducted heat pump and other R-454B versionsBosch IDS Plus product page. Checked November 23, 2026.
LGR-32 in its split systemsLG HVAC "Why R-32" page. Checked November 23, 2026.
SamsungR-454B in the Hylex heat pump; other lines not confirmed on Samsung's siteSamsung HVAC Hylex page. Checked November 23, 2026.
Fujitsu GeneralR-32 in AIRSTAGE ductless heat pumpsFujitsu General America R-32 page. Checked November 23, 2026.
AAONR-454B configurable across its commercial productsAAON R-454B announcement, May 14, 2024. Checked November 23, 2026.

For a commercial account, your supplier relationships mostly set your refrigerant. A shop that installs Trane rooftop units and Daikin ductless systems will stock and recover both.

R-32 vs R-454B comparison table

The table compares the two refrigerants on 14 points, each from a first-hand source.

PropertyR-32R-454B
ASHRAE 34 safety classA2L, lower flammability: Arkema R-32 guideA2L: Chemours Opteon XL41 data
GWP, EPA Technology Transitions table (100-year)675465 (marked Calculated): EPA table
GWP, IPCC AR4 basis used in supplier literature675; EPA states its HFC values match AR4466: Chemours data
CompositionSingle component, difluoromethaneBlend of R-32 / R-1234yf, 68.9% / 31.1% by mass
Temperature glideNoneAbout 1.5 K (2.7°F)
Discharge pressure vs R-410AAbout 2% higher: 414 vs 405 psi at 45°F evaporating and 110°F condensingAbout 140 kPa (20 psi) lower at 104°F (40°C) condensing
Charge vs R-410AUp to 30% smaller, depending on model: DaikinMass flow about 20% lower; Chemours publishes no charge percentage
Cooling capacity vs R-410AAbout 10% more: Daikin−3% to +3% in Chemours' calculated cycle
Efficiency vs R-410A, as the maker states it5–10% better, depending on model: DaikinCOP +2% to +7% in Chemours' calculated cycle
Burning velocity6.7 cm/s5.2 cm/s; lower flammability limit 0.303 kg/m³
CylinderGray RAL 7044 body with a red band, like every flammable refrigerant: AHRI Guideline NSame gray body and red band
2025 supplyNot compared hereCylinder shortage from spring 2025; distributors reported better supply by September 2025 (2025 historical reporting; not current pricing): ACHR News
Typical U.S. equipmentDuctless, split AC and heat pumps, light commercial, VRV (Daikin)Mini-splits, ducted splits, PTACs, multi-splits, DX chillers (Chemours); Trane rooftops
Headroom under the 700 GWP limit in 40 CFR 84.5425 points235 points

We found no reliable public 2026 cylinder price for either refrigerant as of November 23, 2026. Get a current written quote before you bid. R-410A, for reference, is 2,088 on the same EPA table.

Fig. 1

R-32 has 25 points of headroom under the 700 limit; R-454B has 235

  • R-32
  • R-454B

GWP, EPA table

R-32 675R-454B 465

Headroom under the 700 limit

R-32 25 pointsR-454B 235 points

Reported price per 20 lb (one online retailer, May 28, 2025)

R-32 $449R-454B $2,799

Show the data
MeasureR-32R-454B
GWP, EPA table675465
Headroom under the 700 limit25 points235 points
Reported price per 20 lb$449$2,799
Source: EPA Technology Transitions GWP reference table; 40 CFR 84.54Each row has its own scale.

Commercial equipment examples by job

Treat these as starting points for a model-by-model submittal review. Product families, options and refrigerants vary by market and model; verify the nameplate and current manufacturer literature for the exact matched system.

Job settingEquipment formExample commercial product lines and refrigerantContractor preparation
Office or retail replacement with roof accessPackaged rooftop unit (RTU)Carrier WeatherMaster 50GE: R-454B; Trane Precedent: R-454B. Carrier 50GE; Trane PrecedentMatch the curb, capacity and controls; confirm the selected model's certified IEER and safety accessories in its submittal.
Multi-zone tenant areas or smaller commercial spacesDuctless / VRF-style systemsDaikin's commercial VRV EMERION line uses R-32. Daikin commercial product announcement. Verified November 20, 2026.Confirm indoor/outdoor match, total circuit design, approved line lengths and the exact A2L mitigation requirements for the equipment listing.
Small commercial room or retrofit with existing line-set constraintsSplit systemCarrier's light-commercial transition includes R-454B. Carrier 50GECheck model compatibility and permitted line-set reuse; record factory charge and the line length included in that charge before quoting field-added refrigerant.

The examples show why a brand name alone is not a refrigerant specification. Verify the refrigerant on current manufacturer literature for the exact matched system.

Compare the equipment, not only the refrigerant

For the actual matched indoor and outdoor models, compare certified SEER2 for applicable split equipment and IEER for rooftop equipment in the AHRI Directory. Then compare the manufacturer's submittals for factory charge, the line length covered by that charge, and any required field addition. Confirm the A2L sensor, control and ventilation requirements in the equipment listing and installation instructions, then compare parts and compressor warranty terms for the quoted models. A refrigerant-level comparison cannot substitute for these model-specific values.

Contractor ownership cost

Build the estimate from current written refrigerant quotes rather than the old one-day cylinder examples in this article. Date each supplier quote, note the container size and unit price, and price the expected field top-up from the manufacturer's charge instructions. Include the shop's A2L-approved recovery and detection tools, separate identified recovery cylinders for each refrigerant, crew training time and ongoing stock needs. If work spans both refrigerants, budget to keep both tool and cylinder setups available; do not assume one refrigerant's gear or recovered contents can serve the other. For refrigerant purchases, check the EPA Section 608 sales requirements.

Your situationA practical selection check
Your existing service base is concentrated in one manufacturerCompare its current matched models, AHRI ratings, charge instructions and local availability first.
You service both rooftop and ductless equipmentCompare the models for each job separately and plan for both refrigerants, tools and crew procedures where required.
The owner prioritizes lower refrigerant GWPCompare the EPA table values and the equipment actually available for the application; R-454B is 465 and R-32 is 675 on EPA's table.
You are considering reusing an R-410A system or componentsGet a model-specific manufacturer decision; neither R-32 nor R-454B is a drop-in R-410A replacement.

GWP basis: EPA's Technology Transitions table lists R-454B at 465 (calculated) and R-32 at 675; Chemours' product information gives R-454B as 466 on an IPCC AR4 basis. Keep the basis with the figure instead of treating the two R-454B values as conflicting measurements. EPA table; Chemours Opteon XL41 product information. Verified 2026-11-20.

Safety correction: R-454B is not nonflammable: ASHRAE classifies it A2L, the lower-flammability class. Neither R-454B nor R-32 is a drop-in replacement for R-410A; use only the refrigerant specified for the complete equipment model. ASHRAE Standard 34 addendum; DOE-hosted comparison. Verified 2026-11-20.

Pros and cons of each refrigerant

Each refrigerant wins on different points, so match them to the job.

R-32R-454B
ProsSingle component with no glide, so a leak leaves the remaining charge unchanged; about 10% more capacity; up to 30% less charge; much cheaper per pound in 2025Lowest GWP of the two (465), with 235 points of room under the 700 limit; pressure and capacity close to R-410A, so crews see familiar readings; used by most U.S. ducted brands; Chemours says it can be topped off after leaks
ConsGWP 675 sits only 25 points under the 700 limit; discharge runs about 36°F hotter than R-410A at the same conditions; faster burning velocity (6.7 vs 5.2 cm/s); fewer U.S. ducted brandsA blend with about 1.5 K glide; cylinders ran short and prices spiked in 2025; costs more per pound

The 25-point margin matters if limits tighten later. Today both meet the rule for new residential and light-commercial equipment.

Which is more efficient: R-32 or R-454B?

R-32 has a small edge at the refrigerant level: Daikin states 5–10% better efficiency than R-410A, while Chemours calculates 2–7% for R-454B. No manufacturer sells the same equipment series in both refrigerants, so a like-for-like SEER2 test does not exist.

The equipment tier moves efficiency far more than the refrigerant does. Goodman's R-32 split line runs up to 19.0 SEER2, and Rheem builds R-454B units at 13.4 and 14.3 SEER2. That spread is several times larger than the few-percent refrigerant difference.

For efficiency, compare the SEER2, EER2 or IEER of the models in the bid. On a rooftop job, ask for the IEER at the building's load profile; Trane's R-454B Precedent heat pumps are rated up to 17.5 IEER.

What the choice means for contractors

Plan tools, training and stock for both refrigerants if you service more than one brand.

Tools

Use recovery machines, leak detectors and vacuum pumps that their makers approve for A2L refrigerants. A2L cylinders over 2.2 lb carry a relief valve rather than a rupture disc, according to the Arkema R-32 guide. Keep a separate, labeled recovery cylinder for each refrigerant.

Training

Train crews on each model's installation instructions, including the leak sensors and mitigation controls that UL 60335-2-40 requires. Expect hotter discharge readings on R-32 equipment and set diagnostic targets from the maker's charging chart. Fill lubricant with the oil the unit maker specifies.

Inventory

Confirm current cylinder stock and lead times with your distributor before scheduling work; reported 2025 constraints are historical. Check factory pre-charge against line length: Rheem raised the pre-charge on some R-454B units in May 2025 to cover a 30-foot line set. Buying requires EPA Section 608 certification evidence for your technicians.

Service agreements

Name the refrigerant, charge and recovery responsibility for each unit in the contract. Clauses 6 and 7 of our HVAC service agreement template cover certification, recovery and the 2026 leak rule. The commercial HVAC maintenance contracts guide explains which equipment that leak rule reaches.

Find replacement jobs and quotes

Every RTU or chiller swap after 2025 is a refrigerant decision, and many start with a permit. The HVAC permits guide explains when equipment replacement needs one.

For contractors planning replacement work, commercial HVAC lead generation explains how public project signals can help identify opportunities.

See new permits in New York, free

FAQ

Which is better for a commercial rooftop unit, R-32 or R-454B?

Neither refrigerant is a universal winner for a rooftop replacement. Compare the listed unit models, certified IEER, capacity, charge instructions, A2L controls and local availability for the job.

Which refrigerant does my brand use?

Check the outdoor unit nameplate and the exact model’s current manufacturer submittal. A brand can sell different refrigerants across product families and markets, so do not identify the charge from the brand name alone.

Do R-32 and R-454B cool differently?

Both can cool a building when used in equipment designed and listed for that refrigerant. The refrigerant alone does not tell you how a particular system will perform; compare the matched models’ capacity and certified efficiency ratings.

Can I mix R-32 and R-454B?

No. They are different refrigerants, and charging one into equipment specified for the other can leave the system with the wrong refrigerant composition. Follow the nameplate and manufacturer service instructions; do not treat liquid charging as permission to mix them.

Can I put R-32 or R-454B in an existing R-410A system?

No. Neither is a drop-in replacement for an R-410A system. Use only the refrigerant specified for the complete matched equipment model; a conversion requires manufacturer-approved equipment and instructions.

Why would R-32 and R-454B mix if a technician charges liquid?

Liquid charging does not make two different refrigerants interchangeable. If the wrong refrigerant enters a circuit, stop and follow the equipment manufacturer’s recovery and service procedure rather than topping off or guessing at the composition.